Hays Cleveland Air Flow Switch. Manual Reset .05-12" WC.
The Model AFS-460 is a general purpose
proving switch designed to require
manual operator reset following actuation.
It can be used to sense positive,
negative, or differential air pressure in
HVAC and Energy Management applications
which require operator interface.
|
Customer Rating: Not Rated Yet Quick Order Number: 174 Manufacturer: Hays/Cleveland Controls Part Number: 25060 Weight: 1.25 lbs Stocked Item*: Yes Quantity Available*: 19 Price: $53.76 * If an order is placed where the item is a "Non-Stocked Item" or the quantity ordered is more than the quantity available, all items in stock will be shipped and the remainder of the items will be shipped as soon as we get the "backordered" items in. |
Sample Media: Air. Mounting Position (in order to
meet lowest operating
specifications): Diaphragm in any
vertical plane.
Field Adjustable Range: 0.40 ±
0.06"w.c. to 12.0"w.c.
Switch Differential: Progressive,
increasing from approximately
0.06± 0.01"w.c. at minimum set
point, to approximately 0.8"w.c. at
maximum set point.
Maximum Pressure: 0.5 psi
(0.03 bar)
Operating Temperature Range:
-40 to 180F (-40.0 to 82.2C)
Life: Exceeds UL-recognized
mechanical endurance test of
6,000 cycles minimum at 0.5 psi
maximum pressure each cycle
and at maximum electrical load.
Electrical Rating: @ 60 Hz.
15 amp 125, 250, or 277 VAC
¼ hp 125 V AC, ½Hp 250 VAC,
½ amp 125 V DC,
¼ amp 250 V DC .
Contact Arrangement:
SPST?NC(manual reset).
Electrical Connections: Screw
top terminals with cup washers.
Sample Line Connections:
Ferrule and nut compression type
connectors will accept 0.25" OD
rigid tubing.
Shipping Weight: 2 |
AFS-460 (download) |